Building Regulations · Guide 14

Solid wall thickness

Approved Document A · Walls · 2C6, Table 3 · Published 11 October 2026

One house end wall that grows, as a 1:10 scale model on a real trench and foundation. A height pole marks Table 3's lines (3.5, 9 and 12 m) from the top of the concrete, below ground. The wall goes up three storeys (8.9 m): 190 mm all the way. A gable takes it to 10 m (measured half way up the gable), so the ground storey must be 290 mm, base to first floor. Made 11.5 m long, it needs 290 mm for the bottom two storeys. Full-size slices beside it show the solid wall going from 190 to 290, and the same storey as a cavity wall, where the two leaves plus 10 mm must reach the solid figure.

The build

Solid wall thickness: the finished build
1Where height is measured from

One house wall that grows, as a scale model (1:10), with full-size slices of its bottom storey beside it. Height is measured from the top of the concrete foundation, below ground. Storeys are 2.7 m floor to floor, the most Diagram 8 shows, and the ground floor is taken to brace the wall. Lengths and heights are examples. Solid external, compartment or separating walls in coursed brick or block, in a building that meets the other Section 2C conditions; cavity walls use the same figures through 2C8. "Up to" includes the figure itself. Section 2C covers residential buildings of up to three storeys (and small single-storey non-residential buildings and annexes), so a wall over 9 m high is usually a gable wall; its height is measured to half way up the gable (Diagram 8).

Step by step

The source

What Approved Document A says

The pages of Approved Document A this guide relies on, in the order they come up in the build. Each clause is highlighted; the notes beside the page follow as you read.

Approved Document A, page 14
Approved Document A, page 16
Approved Document A, page 17
Approved Document A, page 25
Approved Document A, page 18
Approved Document A, page 22

Approved Document A: Structure (2004 edition incorporating 2010 and 2013 amendments). Crown copyright, reproduced under the Open Government Licence v3.0. Highlights and notes are ours.

Good to know

Also in this section, not shown here

AD A 2C4, Diagram 1 and Section 2C scope
residential buildings of not more than three storeys, with size and proportion limits.
AD A 2C11 and Diagram 4
parapet wall thickness and height.
AD A 2C12
90 mm single leaf for small single-storey non-residential buildings and annexes.
AD A 2C14 to 2C16
maximum floor areas, imposed loads and building height.
AD A 2C26 and 2C27
buttressing wall thickness and piers that give end restraint.
AD A 2C24
loading conditions on the wall.

Examples and other sources

  • Scale 1:10, 2.7 m storeys, the gable drawn in steps: drawing choices; 2.7 m is the most Diagram 8 shows.
  • The ground floor is taken to brace the wall, so the ground storey is measured from the ground floor (A1): an assumption of the model.
  • The 290 mm running from the base of the wall up to first-floor (or second-floor) level: our reading of 'from the base for the height of one storey'; it covers the whole storey.
  • The 290 mm base shown sticking out 50 mm each side: a drawing choice; AD A does not say which face the extra thickness goes on.
  • Reading that a wall over about 9 m in a house is usually a gable wall: our interpretation of Section 2C and Diagram 8.
  • Brick and block sizes in the cavity slice (102.5, 100, 190): examples.
  • 1/16 worked examples (169 mm at 2.7 m, 219 mm at 3.5 m, 232 mm at 3.7 m): our arithmetic.
  • The British Standard for modular units in 2C13 is not named in AD A.

This guide explains Approved Document A (2013 edition, with 2010 and 2013 amendments) for England. It is general guidance, not professional advice: check your own project with Building Control or a structural engineer.

Tell us about the building.

Send an address and a line about what you need. We aim to reply within one working day to discuss the next step and arrange a site visit where needed.